About the gateway
The gateway receives data from Mini sensors over Bluetooth and forwards it to Argos through your plant network. It is housed in a compact aluminium enclosure with external antennas.
The Argos gateway: a black aluminium box with two antennas on one end.
Ports and lights
Section titled “Ports and lights”All connectors, the status lights and the button are on the same end of the enclosure.
The two antennas are on the opposite end: Wi-Fi on the left and the sensor radio on the right. The meaning of each light is described in What the lights mean, and the button in Button and reset.
What you need
Section titled “What you need”| Item | Requirement |
|---|---|
| Power supply | 5 V DC, at least 1 A, with a 5.5 × 2.1 mm plug, center positive. A USB port does not supply enough current. |
| Network | An Ethernet cable or a 2.4 GHz Wi-Fi network. |
| Internet access | Outbound HTTPS to api.argossense.com on port 443. |
| Phone | The Argos app with Bluetooth turned on. Required only for Wi-Fi setup. |
Where to put it
Section titled “Where to put it”A gateway mounted high on a pillar in a factory hall, with a clear view of the machines around it.
Radio range depends on the line of sight between the gateway and the sensors. For the best coverage:
- Mount the gateway high, above the machines.
- Place it centrally among the sensors it serves.
- Keep a clear line of sight to the sensors where possible.
- Never install it inside a metal cabinet, which blocks the radio signal.
- Install it indoors in a dry location. The enclosure is not waterproof.
Network limitations
Section titled “Network limitations”The gateway does not support:
- Static IP addresses. The network must assign an address by DHCP.
- Proxy servers.
- Networks with a login page (captive portal).
- WPA2-Enterprise Wi-Fi with per-user credentials.
- 5 GHz Wi-Fi.
If your plant network requires any of these, use an Ethernet connection or ask your IT team for a device network without them.